REPSA Yellow Coat

Clavija y receptáculo Pin & Sleeve 20 Amp., con recubrimiento de PVC

Description

Locations where receptacles are used with stationary or portable electrical devices, such as: Lighting systems, Conveyors, Heaters, Motor generator sets, Air conditioners, Compressors and pumps.
Locations with humid or corrosive conditions

Features

  • External PVC coating of 0.040¨ nominal.
  • 0.002¨ nominal yellow urethane interior coating.
  • Yellow urethane protection on the threads.
  • With PVC sleeves to ensure sealing.
  • Made of copper-free aluminum (4/10 of 1% max).
  • Malleable iron mounting box.
  • Compatible with plugs from other brands.

Exterior coating features

Hardness.

80-84 (Shore A Durometer).

Dielectric strength.

400 Volts/Mil at 60 cycles.

Aging.

1000 hours (Atlas wet UV chamber).

Elongation.

200% min.

Temperature.

Polyvinyl chloride has a crystallization temperature of 5° F (-15° C).

Flammability.

PVC coating will burn if exposed to continuous flame or heat above 400°F (204°C).

Toxicity.

Prolonged exposure to temperatures greater than 200°F (93°C) or fire may cause the PVC coating to release emissions potentially hazardous to the health of those exposed to them.

Receptáculo CPS a prueba de explosión con recubrimiento de PVC REPSA Yellow Coat®
Certifications and compliances.

Plug: Catalog RYC-CPP516

Download data sheet

20 Amp Pin & Sleeve Plug and Receptacle with PVC outer coating and REPSA Yellow Coat® inner Yellow Urethane

Receptacle Ordering Information

WP Table Builder

† Boxes are supplied in malleable iron as standard, to order copper-free aluminum boxes add the suffix “SA” at the end, example: RYC-CPS152101SA.

Specify this product in your project:

CPS receptacle, made of (specify material: copper-free aluminum or malleable iron), for Class I, Division 1 and 2, Groups C and D areas; 2 Wires 3 Poles, in box (specify Dead - End or Feed - Thru), of (specify diameter, e.g.: 3/4”Ø), capacity of 125 – 250 Vac, 1 HP of 20 Amp. @ 18 Vcd, with exterior PVC coating and interior with yellow urethane, and encapsulated stainless steel screws, REPSA Yellow Coat®.

CPP plug, made of copper-free aluminum, for Class I, Division 1 and 2, Groups C and D areas; 2 Wires 3 Poles, capacity of 125 – 250 Vac, 1 HP of 20 Amp. @18 Vcd, with exterior PVC coating and interior with yellow urethane, REPSA Yellow Coat®.