Menu
REPSA Yellow Coat® PVC coated standard radius elbow are more efficient, faster, economical and easier to install, saving you time bending the pipe, avoiding waste of materials during installation and helping you with changes direction in the conduit piping system.
80-84 (Shore A Durometer).
400 Volts/Mil at 60 cycles.
1000 hours (Atlas wet UV chamber).
200% min.
Polyvinyl chloride has a crystallization temperature of 5° F (-15° C).
PVC coating will burn if exposed to continuous flame or heat above 400°F (204°C).
Prolonged exposure to temperatures greater than 200°F (93°C) or fire may cause the PVC coating to release emissions potentially hazardous to the health of those exposed to them.
Conduit curve with exterior PVC coating and interior of REPSA Yellow Coat® Urethane
Trade Size (Inches) | Galvanized Steel | Aluminium | Outside diameter with PVC (inch) | Nominal inside diameter | Total length of curve in inches | Radius in inches (r) | Length to center in inches (C) | Straight end length in inches (D) |
1/2” | RYC-CRV50 | RYC-CRV50AL | 0.920 | 0.622 | 11 1/4” | 4.00 | 6.50 | 2.12 |
3/4” | RYC-CRV75 | RYC-CRV75AL | 1.130 | 0.824 | 12 1/2” | 4.50 | 7.25 | 2.75 |
1” | RYC-CRV100 | RYC-CRV100AL | 1.395 | 1.049 | 14 3/4” | 5.75 | 8.63 | 2.88 |
1-1/4” | RYC-CRV125 | RYC-CRV125AL | 1.740 | 1.380 | 17 3/4” | 7.25 | 10.44 | 3.19 |
1-1/2” | RYC-CRV150 | RYC-CRV150AL | 1.980 | 1.610 | 19 3/4” | 8.25 | 11.63 | 3.38 |
2” | RYC-CRV200 | RYC-CRV200AL | 2.455 | 2.067 | 22 1/2” | 9.50 | 13.31 | 3.81 |
2-1/2” | RYC-CRV250 | RYC-CRV250AL | 2.955 | 2.469 | 28” | 10.50 | 16.50 | 5.75 |
3” | RYC-CRV300 | RYC-CRV300AL | 3.580 | 3.068 | 32” | 13.00 | 18.75 | 5.79 |
4” | RYC-CRV400 | RYC-CRV400AL | 4.580 | 4.026 | 39 1/2” | 16.00 | 23.18 | 7.96 |
Standard 90º radius elbows, substitute the numbers 30, 45, or 60 after the letters “CRV” to change the degrees of the elbow, axis: RYC-CRV45200AL.
For other sizes and special radius, consult your distributor.
Copper-free aluminum or Galvanized steel elbow, schedule 40, standard 90° radius, (specify diameter, e.g.: 3/4”Ø), with exterior PVC coating, and interior with yellow urethane, includes plugs for protection of threads, REPSA Yellow Coat®.